Monthly fire extinguisher inspection checklist
Use this list on every extinguisher once a month (about every 30 days). It takes under a minute per unit. Initial and date the unit's tag or your log when you're done.
Check each unit for
- In its assigned place. The extinguisher is where it belongs, mounted or in its cabinet.
- Visible and easy to reach. Nothing blocks it, and the sign or marker can be seen.
- Instructions facing out. The operating label can be read from the front.
- Pin and tamper seal intact. The safety pin is in place and the seal isn't broken or missing.
- Pressure gauge in the green. For stored-pressure units, the needle is in the operable range.
- Full. It feels the right weight when lifted (or is weighed if your procedure requires it).
- No visible damage. No dents, corrosion, leaks or a clogged nozzle, and the hose isn't cracked.
- Tag or label current. The service tag shows the last annual maintenance and is still in date.
If a unit fails any item, take it out of service or have it serviced by a qualified technician, and note it in your log.
What comes due besides the monthly check
| Task | How often | Who |
|---|---|---|
| Monthly inspection (this checklist) | About every 30 days | Trained staff or owner |
| Annual maintenance | Every 12 months | Qualified technician |
| 6-year maintenance | Every 6 years for stored-pressure dry chemical and clean agent units | Qualified technician |
| Hydrostatic test | Every 5 years (water, foam, CO2, wet chemical) or 12 years (dry chemical, clean agent) | Qualified technician |
These follow common NFPA 10 requirements. Your local fire authority may require more. This page is guidance, not a substitute for your authority's rules.